Failure |
Describtion |
Solution |
Manual start failure |
Press the ENT key£¬the green light isn¡¯t bright on the aboved and the motor doesn¡¯t work. |
Check whether the greenlight is broken,if the LED light isn¡¯t broken,please contact with the factory;If the LED light is broken,please see below solution. |
Press the ENT key£¬the green light is bright on the aboved and the motor doesn¡¯t work. |
Check the menu of¡°low oil pressure¡±in the ¡°input port state¡±,if display ¡°0¡±,please check whether the oil pressure sensor is ok;if display ¡°1¡±,the oil pressure sensor is ok,now please press START,measuring the module port 34 ¡°start¡± whether there¡¯s 24V with a multimeter,if the voltage is 24V,check whether the outside middle relay,start moter is broken,and whether the battery voltage is enough;If port 34 no output,the module might be damaged. |
|
Auto start failure |
Module in Auto state,inspection ¡°remote start¡± have input, the ¡°remote start¡± state light isn¡¯t bright and the motor doesn¡¯t work. |
Check the? menu of ¡°remote start¡± in the¡°input state¡±,if the ¡°remote start¡± display ¡°0¡± means that the outside timer etc module relay is broken cause didn¡¯t receive the input signal;If display ¡°1¡±,the module might be broken. |
Module in Auto state,inspection ¡°remote start¡± have input, ?the ¡°remote start¡± state light is bright on and the motor doesn¡¯t work. |
Check the oil pressure sensor; Switch to the manual start, check whether there¡¯re output signal of the port 34- ¡°remote start¡±, the outside components and the battery voltage. |
|
Wheel tooth is fighting when start |
Start successful and motor keep running, the whell tooth is fighting. |
Lower down the trip speed; Suggest used speed sensor to get the rotate speed. |
On load current display incorrect. |
Current ratio setting incorrected. |
Reset the current ratio. |