| Failure | Describtion | Solution | 
| Manual start failure | Press the ENT key£¬the  green light isn¡¯t bright on the aboved and the motor doesn¡¯t work. | Check whether the  greenlight is broken,if the LED light isn¡¯t broken,please contact with the  factory;If the LED light is broken,please see below solution. | 
| Press the ENT key£¬the  green light is bright on the aboved and the motor doesn¡¯t work. | Check the menu of¡°low  oil pressure¡±in the ¡°input port state¡±,if display ¡°0¡±,please check whether the  oil pressure sensor is ok;if display ¡°1¡±,the oil pressure sensor is ok,now  please press START,measuring  the module port 34 ¡°start¡± whether there¡¯s 24V with a multimeter,if the voltage  is 24V,check whether the outside middle relay,start moter is broken,and whether  the battery voltage is enough;If port 34 no output,the module might be damaged. | |
| Auto start failure | Module in Auto state,inspection  ¡°remote start¡± have input, the ¡°remote start¡± state light isn¡¯t bright and the  motor doesn¡¯t work. | Check the? menu of ¡°remote start¡± in the¡°input state¡±,if  the ¡°remote start¡± display ¡°0¡± means that the outside timer etc module relay is  broken cause didn¡¯t receive the input signal;If display ¡°1¡±,the module might be  broken. | 
| Module in Auto state,inspection ¡°remote start¡± have input, ?the ¡°remote start¡± state light is bright on and  the motor doesn¡¯t work. | Check the oil  pressure sensor; Switch to the manual start, check whether there¡¯re output  signal of the port 34- ¡°remote start¡±, the outside components and the battery  voltage. | |
| Wheel tooth is  fighting when start | Start successful and  motor keep running, the whell tooth is fighting. | Lower down the trip speed;Suggest used speed sensor to get the rotate speed. | 
| On load current  display incorrect. | Current ratio setting  incorrected. | Reset the current  ratio. | 